? Make sure you know your system voltage, battery compartment size (length, width and height) and your energy needs.
? Determine whether you want to use a deep cycle flooded, Deep-Cycle Gel or Cycling AGM battery.
Step 1: Determine your battery voltage and how many to use
1-1 Based on your system voltage, you must first decide which battery is needed and how many to use in order to meet your requirements. For example, you may connect a series of eight 6V batteries, six 8V batteries or four 12V batteries for a 48-volt system. The size of your battery compartment, your performance requirements and costs may limit your options.
1-2 Make sure there is enough space between batteries to allow for minor battery expansion that occurs during use and to allow proper airflow to keep battery temperature down in hot environments.
TIP: Connecting batteries in series does not increase the capacity of the batteries; it simply increases the overall voltage to meet your system requirements. Once your voltage requirements are met, if space allows you can double the batteries in a parallel connection?thereby doubling your battery capacity. See diagrams below.
Series Connect | |
To increase voltage, connect batteries in series. This will not increase the system capacity.
Example : |
To increase voltage, connect batteries in series. |
Parallel Connect | |
To increase capacity, connect batteries in parallel. This will not increase the system voltage.
Example : |
To increase amp-hour capacity, connect batteries in parallel. |
Series/Parallel Connect | |
To increase both voltage and capacity, connect additional batteries in series and parallel. Example : |
To increase both voltage and amp-hour capacity, connect batteries in series/parallel. |
Step 2: Choose your best battery model
2-1 When choosing your battery model, first consider your battery compartment space as this may limit your options. Within your size restrictions you may have several battery options to choose from. For example, you can use a T-105 or T-125 in the same space, as they are the exact same physical size. The difference between these batteries is the amount of energy they have to offer.
2-2 Next consider your energy needs. If replacing an existing battery, use it as a reference point. If your old battery provided enough energy, it can be replaced with a similar capacity battery. If you need more energy you can size up, or if you need less energy you can size down.
TIP: If you do not know what battery to use, contact your equipment manufacturer for their recommended battery specification. Trojan Battery also offers outstanding technical support provided by full-time applications engineers to help you select your ideal batteries.
Step 3: Select your best terminal
3-1 Finally determine which terminal option best meets your needs based on the type of cable connections you plan to use. Look for the terminal(s) available for the battery you have selected. (Please see the back page of this guide for available terminals to make your selection.)
There are two popular construction types: flooded batteries (wet) and VRLA batteries (Valve Regulated Lead Acid). In the flooded types, the electrolyte is a solution of sulfuric acid and water that can spill out if the battery is tipped over. In VRLA batteries, the electrolyte is suspended in a gel or a fiberglass-mat (AGM technology), allowing these batteries to be mounted in a variety of positions.
Recommended Equipment:
|
|
CAUTION: Always wear protective clothing, gloves, and goggles when handling batteries, electrolyte, and charging your battery.
Batteries should be carefully inspected on a regular basis in order to detect and correct potential problems before they can do harm. It is a great idea to start this routine when the batteries are first received.
Inspection Guildlines:
1. Examine the outside appearance of the battery.
- Look for cracks in the container.
- The top of the battery, posts, and connections should be clean, free of dirt, fluids, and corrosion. If batteries are dirty, refer to the Cleaning section for the proper cleaning procedure.
- Repair or replace any damaged batteries.
2. Any fluids on or around the battery may be an indication that electrolyte is spilling, leaching, or leaking out.
- Leaking batteries must be repaired or replaced.
3. Check all battery cables and their connections.
- Look closely for loose or damaged parts.
- Battery cables should be intact; broken or frayed cables can be extremely hazardous.
- Replace any cable that looks suspicious.
Proper Torque Values for Connection Hardware:
Flooded | Automotive 50-70 in-lbs Side 70-90 in-lbs Wingnut 95-105 in-lbs LPT 95-105 in-lbs Stud 120-180 in-lbs LT 100-120 in-lbs |
VRLA | Button 90 to 100 in-lbs LT 100-120 in-lbs |
WARNING: Do not overtighten terminals. Doing so can result in post breakage, post meltdown, or fire. |
I. Specific Gravity Test The readings should be at or above the factory specification of 1.277 +/- .007. If any specific gravity readings register low, then follow the steps below. If any specific gravity readings still register low then follow the steps below. If any specific gravity reading still registers lower than the factory specification of 1.277+/- .007 then one or more of the following conditions may exist: II. Open-Circuit Voltage Test TABLE 1. State of charge as related to specific gravity and
Visual inspection alone is not sufficient to determine the overall health of the battery. Both open-circuit voltage and specific gravity readings can give a good indication of the battery's charge level, age, and health. Routine voltage and gravity checks will not only show the state of charge but also help spot signs of improper care, such as undercharging and over-watering, and possibly even locate a bad or weak battery. The following steps outline how to properly perform routine voltage and specific gravity testing on batteries.
(Flooded batteries only)
1. Do not add water at this time.
2. Fill and drain the hydrometer 2 to 4 times before pulling out a sample.
3. There should be enough sample electrolyte in the hydrometer to completely support the float.
4. Take a reading, record it, and return the electrolyte back to the cell.
5. To check another cell, repeat the 3 steps above.
6. Check all cells in the battery.
7. Replace the vent caps and wipe off any electrolyte that might have been spilled.
8. Correct the readings to 80o F:
9. Compare the readings.
10. Check the state of charge using Table 1.
1. Check and record voltage level(s).
2. Put battery(s) on a complete charge.
3. Take specific gravity readings again.
1. Check voltage level(s).
2. Perform equalization charge. Refer to the Equalizing section for the proper procedure.
3. Take specific gravity readings again.
1. The battery is old and approaching the end of its life.
2. The battery was left in a state of discharge too long.
3. Electrolyte was lost due to spillage or overflow.
4. A weak or bad cell is developing.
5. Battery was watered excessively previous to testing.
Batteries in conditions 1 - 4 should be taken to a specialist for further evaluation or retired from service.
For accurate voltage readings, batteries must remain idle (no charging, no discharging) for at least 6 hrs, preferably 24 hrs.
1. Disconnect all loads from the batteries.
2. Measure the voltage using a DC voltmeter.
3. Check the state of charge with Table 1.
4. Charge the battery if it registers 0% to 70% charged.
If battery registers below the Table 1 values, the following conditions may exist:
1. The battery was left in a state of discharge too long.
2. The battery has a bad cell.
Batteries in these conditions should be taken to a specialist for further evaluation or retired from service.
open circuit voltage
80o F
There are six simple steps in testing a deep cycle battery-inspect, recharge, remove surface charge, measure the state-of-charge, load test, and recharge. If you have a non-sealed battery, it is highly recommended that you use a good quality temperature compensated hydrometer.
1. INSPECT
Visually inspect for obvious problems.
2. RECHARGE
Recharge the battery to 100% state-of-charge.
3. REMOVE SURFACE CHARGE
Surface charge is the uneven mixture of sulfuric acid and water within the surface of the plates as a result of charging or discharging. It will make a weak battery appear good or a good battery appear bad. You need to eliminate the surface charge by one of the following methods:
3.1. Allow the battery to sit for four to twelve hours to allow for the surface charge to dissipate.
3.2. Apply a load that is 33% of the ampere-hour capacity for five minutes and wait five to ten minutes.
3.3. With a battery load tester, apply a load of at least one half the battery's CCA rating for 15 seconds and wait five to ten minutes.
4. MEASURE THE STATE-OF-CHARGE
If the battery's electrolyte is above 110o F (43.3o C), allow it to cool.
Digital Voltmeter Open Circuit Voltage | Approximate State-of-Charge | Hydrometer Average Cell Specific Gravity | Electrolyte Freeze Point |
12.65 | 100% | 1.265 | -75o F (-59.4o C) |
12.45 | 75% | 1.225 | -55o F (-48.3o C) |
12.24 | 50% | 1.190 | -34o F (-36.7o C) |
12.06 | 25% | 1.155 | -16o F (-26.7o C) |
11.89 | Discharged | 1.120 | -10o F (-23.3o C) |
Electrolyte Temperature Fahrenheit | Electrolyte Temperature Celsius | Add or Subtract to Hydrometer's SG Reading | Add or Subtract to Digital Voltmeter's Reading |
160o | 71.1o | +.032 | +.192 |
150o | 65.6o | +.028 | +.168 |
140o | 60.0o | +.024 | +.144 |
130o | 54.4o | +.020 | +.120 |
120o | 48.9o | +.016 | +.096 |
110o | 43.3o | +.012 | +.072 |
100o | 37.8o | +.008 | +.048 |
90o | 32.2o | +.004 | +.024 |
80o | 26.7o | 0 | 0 |
70o | 21.1o | -.004 | -.024 |
60o | 15.6o | -.008 | -.048 |
50o | 10o | -.012 | -.072 |
40o | 4.4o | -.016 | -.096 |
30o | -1.1o | -.020 | -.120 |
20o | -6.7o | -.024 | -.144 |
10o | -12.2o | -.028 | -.168 |
0o | -17.8o | -.032 | -.192 |
Electrolyte temperature compensation will vary depending on the battery manufacturer's recommendations. If you are using a NON-temperature compensated HYDROMETER, make the adjustments indicated in the table above. For example, at 30 o F (-1.1o C), the specific gravity reading would be 1.245 for a 100% state-of-charge. At 100 o F (37.8 o C), the specific gravity would be 1.273 for 100% state-of-charge. This is why using a temperature compensated hydrometer is highly recommended and more accurate. If you are using a DIGITAL VOLTMETER, make the adjustments indicated in the table above. For example, at 30 o F (-1.1o C), the voltage reading would be 12.53 for a 100% state-of-charge. At 100 o F (37.8 o C), the voltage would be 12.698 for 100% state-of-charge.
For non-sealed batteries, check the specific gravity in each cell with a hydrometer and average the readings.
If the state-of-charge is BELOW 75%, using either the specific gravity or voltage test, or the built-in hydrometer indicates "bad" (usually dark), then the battery needs to be recharged BEFORE proceeding.
4.1. If there is a .05 (sometimes expressed as 50 "points") or more difference in the specific gravity reading between the highest and lowest cell, you have a weak or dead cell(s).
4.2. If the battery will not recharge to a 75% or more state-of-charge level or if the built-in hydrometer still does not indicate "good" (usually green, which is 65% state-of-charge or better).
If you know that a battery has spilled or "bubbled over" and the electrolyte has been replaced with water, you can replace the old electrolyte with new electrolyte and go back to Step 3.2 above.
4.3. If digital voltmeter indicates 0 volts, you have an open cell.
4.4. If the digital voltmeter indicates 10.45 to 10.65 volts, you probably have a shorted cell or a severely discharged battery. A shorted cell is caused by plates touching, sediment ("mud") build-up or "treeing" between the plates.
5. LOAD TEST
If the battery is fully charged or has a "good" built-in hydrometer indication, then you can test the capacity of the battery by applying a known load and measuring the time it take to discharge the battery until 20% capacity is remaining.
6. RECHARGE
If the battery passes the load test, you should recharge it as soon as possible to restore it to peak performance and to prevent lead sulfation.
|
|
1. Check that all vent caps are tightly in place.
2. Clean the battery top with a cloth or brush and a solution of baking soda and water.
- When cleaning, do not allow any cleaning solution, or other foreign matter to get inside the battery.
3. Rinse with water and dry with a clean cloth.
4. Clean battery terminals and the inside of cable clamps using a post and clamp cleaner.
- Clean terminals will have a bright metallic shine.
5. Reconnect the clamps to the terminals and thinly coat them with petroleum jelly (Vaseline) to prevent corrosion.
6. Keep the area around batteries clean and dry.
NOTE: Storing, charging or operating batteries on concrete is perfectly OK.
The most important things to avoid:
1. Freezing. Avoid locations where freezing temperature is expected. Keeping a battery at a high state of charge will also prevent freezing. Freezing results in irreparable damage to a battery's plates and container.
2. Heat. Avoid direct exposure to heat sources, such as radiators or space heaters. Temperatures above 80° F accelerate the battery's self-discharge characteristics.
Step by step storage procedure:
1. Completely charge the battery before storing.
2. Store the battery in a cool, dry location, protected from the elements.
3. During storage, monitor the specific gravity (flooded) or voltage. Batteries in storage should be given a boost charge when they show a 70% charge or less. See Table 1 in the Testing Section.
4. Completely charge the battery before re-activating.
5. For optimum performance, equalize the batteries (flooded) before putting them back into service. Refer to the Equalizing section for this procedure.
There are many types of chargers available today. They are usually rated by their start rate, the rate in amperes that the charger will supply at the beginning of the charge cycle. When selecting a charger, the charge rate should be between 10% and 13% of the battery's 20-hour AH capacity. For example, a battery with a 20-hour capacity rating of 225 AH will use a charger rated between approximately 23 and 30 amps (for multiple battery charging use the AH rating of the entire bank). Chargers with lower ratings can be used but the charging time will be increased.
1. Become familiar with and follow the instructions issued by the charger manufacturer.
2. Batteries should be charged after each period of use.
3. Lead acid batteries do not develop a memory and need not be fully discharged before recharging.
4. Charge only in well-ventilated area. Keep sparks or flames away from a charging battery.
5. Verify charger voltage settings are correct (Table 2).
6. Correct the charging voltage to compensate for temperatures above and below 80o F. (Add .028 volt per cell for every 10o below 80o F and subtract .028 volt per cell for every 10o above 80o F)
Table 2. Charger Voltage Settings for Flooded Batteries
System Voltage | |||||
Charger Voltage Setting |
6V |
12V |
24V |
36V |
48V |
Daily Charge |
7.4 |
14.8 |
29.6 |
44.4 |
59.2 |
Float |
6.6 |
13.2 |
26.4 |
39.6 |
52.8 |
Equalize |
7.8 |
15.5 |
31.0 |
46.5 |
62.0 |
Table 3. Charger Voltage Settings for VRLA Batteries
Charger Voltage Setting |
System Voltage | |||
12V |
24V |
36V |
48V | |
Daily Charge |
13.8 - 14.4 |
27.6 - 28.2 |
41.4 - 42.3 |
55.2 - 56.4 |
Float |
13.5 |
26.4 |
39.6 |
52.8 |
7. Check water level (see the Watering section).
8. Tighten all vent caps before charging.
9. Prevent overcharging the batteries. Overcharging causes excessive gassing (water breakdown), heat buildup, and battery aging.
10. Prevent undercharging the batteries. Undercharging causes stratification.
11. Do not charge a frozen battery.
12. Avoid charging at temperatures above 120o F.
1. Become familiar with and follow the instructions issued by the charger manufacturer.
2. Verify charger has necessary VRLA setting.
3. Set charger to VRLA voltage settings (Table 3).
4. Do not overcharge VRLA batteries. Overcharging will dry out the electrolyte and damage battery.
Many experts recommend that batteries be equalized periodically, ranging anywhere from once a month to once or twice per year. However, Trojan only recommends equalizing when low or wide ranging specific gravity (+/- .015) are detected after fully charging a battery.
Step by Step Equalizing:
1. Verify the battery(s) are flooded type.
2. Remove all loads from the batteries.
3. Connect battery charger.
4. Set charger for the equalizing voltage (Check table 2 in the Charging section above).
5. Start charging batteries.
6. Batteries will begin gassing and bubbling vigorously.
7. Take specific gravity readings every hour.
8. Equalization is complete when specific gravity values no longer rise during the gassing stage.
NOTE: Many chargers do not have an equalization setting so this procedure can't be carried out.
1. Shallow discharges will result in a longer battery life.
2. 50% (or less) discharges are recommended.
3. 80% discharge is the maximum safe discharge.
4. Do not fully discharge flooded batteries (80% or more). This will damage (or kill) the battery.
5. Many experts recommend operating batteries only between the 50% to 85% of full charge range. A periodic equalization charge is a must when using this practice.
6. Do not leave batteries deeply discharged for any length of time.
7. lead acid batteries do not develop a memory and need not be fully discharged before recharging.
8. Batteries should be charged after each period of use.
9. Batteries that charge up but cannot support a load are most likely bad and should be tested. Refer to the Testing section for proper procedure.
% Discharged | |||||
100 |
80 |
60 |
40 |
20 |
0 |
0 |
20 |
40 |
60 |
80 |
100 |
% Charged |
General watering instructions:
- Add water, never acid, to cells (distilled water only )
- DO NOT OVERWATER
- For fully charged standard deep cycle batteries, add water to the level of 1/8 below bottom of vent well (see diagram A below)
- For fully charged Plus Series batteries, add water to the maximum water level indicator (see diagram B below)
- If the batteries are discharged, only add water if the plates are exposed. Add just enough water to cover the plates, then charge the batteries. Once fully charged, add water to the proper level indicated above
- After watering, secure vent caps back on batteries
Diagram A | Diagram B | ||
Add water to 1/8" below bottom of the vent well. |